Single-Flame Source Test Apparatus

The JCKR Small Flame Source Tester is a high-precision ignitability tester engineered to evaluate the reaction-to-fire performance of building materials when subjected to direct flame impingement.

Main Functions:

  • Combustibility & Ignitability Evaluation
  • Automated Ignition & Timing Control
  • Multi-Angle Observation & Data Logging

Testing Standards:

  • ISO 11925-2
  • EN 13501-1 (Class B, C, D, E and F)
  • DIN 4102-1 (Class B2)
  • EN 45545-2
  • DIN 54837
SKU: JCKR

What Is the JCKR Single-Flame Source Test Apparatus?

The JCKR Single-Flame Source Test Ignitability Tester (Also called Small Flame Source Tester or Building Material Combustibility Ignitability Test Apparatus) is a high-precision testing device engineered in compliance with the latest ISO 11925-2 standard. Serving as an advanced Small Flame Source Tester and Ignitability Tester, the JCKR apparatus is designed to support various rigorous fire safety evaluations and classifications including EN 13501-1(Class B, C, D, E and F), DIN 4102-1 (Class B2), EN 45545-2, and DIN 54837.

What Is the Single-Flame Source Test?

The Single-Flame Source Test (also called Small Flame Source Test) is a standardized fire testing method designed to evaluate the ignitability of building products and materials when subjected to direct, small-scale flame impingement. Governed by key international standards such as ISO 11925-2, this test determines a material’s reaction-to-fire behavior, assessing how easily a product ignites and whether flames spread vertically under controlled laboratory conditions.

Applicable Materials of ISO 11925-2 Single-Flame Source Test

  • Applicable to the burning behaviour classification and judgement of building materials, decorative materials, and their products.
  • Mainly used for the evaluation of flame-retardant materials and combustible materials (such as classes B1 and B2).
  • Applicable to essentially flat products and materials evaluated under international standards like EN 13501-1, DIN 4102-1 (Class B2), EN 45545-2, and DIN 54837.

Main Functions and Modules

  • Full stainless-steel cabinet, rust-proof and corrosion-resistant.
  • Large 7-inch industrial intelligent colour touchscreen with an 800*480 resolution and strong anti-interference capability.
  • Double tempered heat-resistant glass doors allowing convenient observation from multiple angles.
  • Motor-driven specimen holder enabling electric raising and lowering of the holder.
  • Electric control of the burner for 45° side tilting and return to the upright position.
  • Flexible burner mobility: moves forward/backward and left/right to adapt to various specimen types.
  • High degree of automation featuring automatic ignition, automatic burner return, automatic timing, and automatic termination.
  • Comprehensive accessories included: standard specimen holders (including melting/shrinking and multi-layer holders), preparation moulds, flame-height gauge, burner positioners, adjustable-speed exhaust fan, and air-velocity sensor.

Technical Parameters of JCKR ISO 11925-2 Single-Flame Source Test Apparatus

ParameterTechnical Specification
Applicable StandardsISO 11925-2, EN 13501-1 (Class B, C, D, E and F), DIN 4102-1 (Class B2) , EN 45545-2, DIN 54837
Electric Power500 W
Burner Inclination Angle45°
Ignition SystemHigh-voltage electronic ignition, automatic ignition and automatic reset
Touchscreen Display7 inches, resolution 800*480 (RAM: 512 M, Storage: 4 G)
Flame Application Time5 s, 15 s or 30 s (automatically selected per test parameters)
Operating EnvironmentTemp: 23℃±5℃ (18℃–28℃); Humidity: 50%±20% (30%–70%)
Gas Supply & Pressure≥95% commercial propane; Pressure: 10 kPa–50 kPa
Power SupplySingle-phase AC 220 V±5%

Important Notes

  • Promptly shut off the gas supply and switch off the power after use.
  • Avoid knocking or impact on the glass observation window.
  • Operate flammable gas carefully; inspect thoroughly during ignition failures to prevent gas accumulation and deflagration.
  • Take proper protective measures and ensure safe storage for gas cylinders and high-pressure tubing.
  • Handle precision components such as the gas flow adjustment knob and air-velocity control valve with care to avoid damage.
  • Ensure adequate ventilation and personal protection against toxic and harmful fumes produced during tests.
  • Equip the test site with sufficient fire-extinguishing equipment.